Service Monitoring Tools Quick Start Guide
Danfoss Turbocor Compressors Inc. 15
M-SM-002-EN Rev. C
1.4.2 Direct Connection
1. Once you have selected Direct as your connection type, select a Serial Port Name. The
items listed in the drop-down labeled Serial Port identify available compressor data streams
- typically, the default (and most likely only) selection is sufficient.
2. If the slave address and baud rate are known, proceed with steps a and b below. If they are
unknown, jump to step 3.
a. enter the known slave address in the Slave Address field and select the known baud
rate from the Baud Rate drop-down list
b. Click Connect. You are now connected. Proceed to Step 4.
3. If the slave address and baud rate are unknown:
a. enter a slave address search range or list of values to test for detection in the Search
Addresses field and click the Search button.
After a short period of time (the less addresses to check, the quicker the search will be),
the search results will appear in the listing field under the Search Addresses field. If no
compressors are detected, No compressors found! will display in the listing; otherwise,
communication setting combinations will appear in the listing.
Figure 15 Compressor Connection Manager - Direct Connection - Search Results
b. Double-click any of the settings combination entries to automatically connect using
those settings - a connection should now be established.